Call to action Contact us Today
Home Air Filtration Dust Collection Contact us Legislation

Loading...

Contact us Today!
104A  Terrace Road, Sebenza, Edenvale

Call to action Follow us on Twitter!

HEPA H13 HIGH CAPACITY FILTER

Multi-V filter HEPA class H13 according to EN1822:2009 (Eintegral ≥ 99,95% - Elocal ≥ 99,75% @E ≥ @ MPPS). The 6V solution (3V for the half size) offers an extended filter surface which allows high nominal air flows.

APPLICATIONS

Airborne solid particles filtration in the air conditioning systems for air contamination controlled environments.

• Hospital Operating Theatres and Intensive Care Units,
• Pharmaceutical Processing,
• Atomic Research,
• Aerospace Engineering,
• Biohazard Atmosphere,
• Genetic and Biological Research,

OPERATING RANGE

Maximum temperature: 80 °C (continuous operation)
Maximum relative humidity: 100%
Recommended final pressure drop: 450 Pa

FILTER MEDIA

HEPA filtration media is fire retardant, water repellent, glass micro fibre paper;
Automated pleating ensures calibrated pleated spacing with continuous thermoplastic thread separators;

TECHNICAL INFORMATION

CONSTRUCTION – HCN9

Galvanised steel frame, complete with side handles.
Polyurethane sealant,  One piece endless gasket.

DISPOSAL

Filter not regenerable.